THE COURSE / M12 THE FAB AS A SYSTEM / M12.1
The fab as a system
After this lesson you can:
- Name a fab's four levels and what each one holds.
- Follow the clean air, the utilities and the wafers through the building.
- Say which areas need the cleanest air, and how much cleaner that is than a room.
Loading the lesson…
Sources
- Intel, "Building Layout and Construction," Intel virtual museum fab tour (read 26 October 2026). Four levels: the interstitial and fan deck, which provide ultra-clean air to the cleanroom; the cleanroom, where the tools are; the sub-fab, with vacuum pumps, chemical valve boxes and life-safety systems; the utility level, with facilities equipment and power distribution. The lithographic side's floor is extra-thick concrete and steel, against vibration.
- CKY Refrigeration & Air Conditioning Engineering Office, "Semiconductor Fab HVAC Design" (14 November 2025). Typical classes by area: lithography and etch ISO 1 to 3, CMP and implant ISO 4 to 5, back-end packaging and test ISO 6 to 7; EUV local environments may need ISO 1. Fan filter coverage 60–80% for ISO 5, 80–100% with ULPA filters for ISO 3 and cleaner. Lithography at 23 ± 0.1 °C, where a 0.1 °C deviation can shift overlay by several nanometres; humidity 45 ± 2%. Make-up air units bring outdoor air down to a 10–12 °C dew point; dry cooling coils in the return air; chilled water at 6–7 °C and 15–18 °C; toxic exhaust ducts at 12–15 m/s; lithography floors to vibration class VC-D or VC-E.
- American Cleanroom Systems, "Cleanroom Classifications (ISO 8, ISO 7, ISO 6, ISO 5)" (read 26 October 2026). ISO 14644-1 limits per m³: ISO 1, 10 particles of 0.1 µm or more; ISO 3, 1,000 (35 of 0.5 µm); ISO 5, 100,000 (3,520 of 0.5 µm); ISO 7, 352,000 of 0.5 µm; ISO 9, 35,200,000 of 0.5 µm. FED-STD-209E Class 1, 10, 100 match ISO 3, 4, 5. Design air changes: ISO 4, 500–600 an hour with 90–100% of the ceiling filtered; ISO 5, 300–480 with 60–70%; ISO 7, 60 with 7–15%.
- H. Hogan, "300mm theory and practice," Solid State Technology (2000). Sealed front-opening unified pods (FOUPs) of 25 wafers, moved by automated material handling; all 300 mm tools have minienvironments, pressurized at least +0.003 in w.c. above the room or contaminants get in; a typical cleanroom ISO 3 to 7; minienvironments let fabs run a less clean room.