THE COURSE / M12 THE FAB AS A SYSTEM / M12.7
Cooling
After this lesson you can:
- Follow a tool's heat out of the building, loop by loop, to the air.
- Say what a chiller does, and what its COP means.
- Explain why the cooling plant has a spare for everything, and keeps running when production stops.
Loading the lesson…
Sources
- International Journal of Low-Carbon Technologies 14(4), 508 (2019): the measured energy use of a fab in Hsinchu. A measured Hsinchu fab: process tools about 54.5 % of its electricity, chillers about 23.5 %, the chillers' COP about 4.5.
- Carrier, AquaEdge 19XR centrifugal liquid chiller catalogue, 300 to 3,400 RT (Asia, March 2025). Fab B's 1,300-ton two-stage sets, the 19XR-8Q81E61: 5,121 x 2,711 x 2,937 mm (pp. 10, 13).
- Commercial Times (工商時報), 3 June 2020: Carrier Taiwan's water-cooled centrifugal chillers enter a wafer fab. The 半導體龍頭 in the Tainan Science Park bought AquaEdge 19XR two-stage chillers.