Skip to content

THE COURSE / M12 THE FAB AS A SYSTEM / M12.8

Power

After this lesson you can:

  • Follow power from the grid to a tool, through the substation and the plant.
  • Say what a voltage dip is, how long one lasts, and what it does to a fab.
  • Say what rides through a dip, what carries a long outage, and the first decisions after one.

Loading the lesson…

Sources

  1. INSIDE, on the Hsinchu voltage dip of 1 March 2022. PSMC recorded a dip of 0.101 s; TSMC 50 to over 100 ms. Read from a search summary; the page refused a direct fetch.
  2. Liberty Times, on the voltage dip at the Hsinchu Science Park, January 2021. Sensitive tools crashed; adjusting and restarting took about half a day or more.
  3. Power Monitors, "Voltage sag analysis: standards, testing and compliance" (on SEMI F47). SEMI F47 sets the voltage sags a semiconductor tool should ride through: to 50 % for 0.2 s, 70 % for 0.5 s, 80 % for 1 s.