THE COURSE / M2 PURE SILICON / M2.9
Where the heat goes
After this lesson you can:
- Say where a crystal puller's heater power ends up, and which of its parts are water-cooled.
- Work out the heat a cooling loop carries from its flow and its temperature rise.
- Follow that heat from the puller through the process cooling water, the chiller and the cooling tower to the air.
Loading the lesson…
Sources
- Komatsu Electronic Metals (now SUMCO TECHXIV), JPH05208888A, cooling system for a single crystal manufacturing device (1993) (read 10 November 2026). The chamber, crucible shaft, heater electrode and seed shaft are water-cooled. "An in-line chiller 3 is provided between the chamber 1 and the cooling water supply device 2." The cooling water temperature is set for each step of the pull, the neck, shoulder, straight body and tail, and for each part; "the accuracy of the crystal shape can be improved, and the crystal yield is improved." Read in Google's machine translation.
- Shin-Etsu Handotai, US10036100B2, apparatus for producing silicon single crystal (read 10 November 2026). The chamber is cooled by a coolant; the heat removed is H = ΔT × L × C × ρ, with ΔT = Tout − Tin, L the coolant's flow in L/s, C = 4.1868 kJ/kg·K and ρ = 0.9970 kg/L for water. The heater power is corrected by the heat removed. Its example repulls a 300 mm crystal with an 1,800 mm body. No flow, temperatures or kW are given.
- Shin-Etsu Handotai, US8764900B2, apparatus and method for producing single crystals (read 10 November 2026). "W (kW) = ΔT (°C) × L (l/min) × 4.1868 (kJ/kg·K) / 60 (sec/min)." "Since a large quantity of water is used, water that has been heated after passing through the inside of the coolant passage and cooling cylinder is cooled in a cooling apparatus, such as a cooling tower or the like, and then the cooled water is temporarily stored in a water tank and re-circulated." Its example charges 320 kg into an 800 mm crucible for a 300 mm crystal.
- Österlund, S., Energy consumption and heating efficiency of Czochralski furnaces (Aalto University thesis, Okmetic Oy, 2025) (read 10 November 2026). Two furnace types at Okmetic, a Finnish wafer maker (200 mm crystals at most). During meltdown, the cooling system used 4.56 and 3.24 kWh per kg of charge; average cooling power 81.19 and 77.02 kW, against an average heater power of 113.14 and 127.39 kW. From its Table 7, the cooling water carried 638.08 of 888.65 kWh (about 72%) for Type 1, and 615.27 of 1014.95 kWh (about 61%, one run) for Type 2: shares worked out by SiliconSim, not stated. Argon carried 1.42% of Type 1's losses. Cooled circuits include the chambers, the crucible shaft, the heater current feedthroughs and electrodes, and the heater power supply.
- GlobalFoundries, US11248822B2, on a fab's process cooling water (read 10 November 2026). A process cooling water loop "that is used only to cool the processing tools"; a chiller "supplies chilled water via another closed chilled water loop to cool the returning process cooling water." The supply "may need to be at a temperature of about 59° F" (15 °C). A logic fab's, not a wafer maker's: the general arrangement.
- ASHRAE Handbook, HVAC Systems and Equipment, chapter 40, Cooling Towers (read 10 November 2026). For each ton of refrigeration "the cooling tower must dissipate an additional 3000 Btu/h of compressor heat", and newer compressors add less. "A portion of the water absorbs heat to change from a liquid to a vapor"; evaporation is "approximately 1% of the water flow rate for each 12.5°F of water temperature range" (about 7 °C).
- US DOE FEMP, purchasing energy-efficient water-cooled electric chillers (read 10 November 2026). Centrifugal chillers' required full-load efficiency is about 0.50 to 0.70 kW of electricity per ton of cooling: a coefficient of performance of about 5 to 7.